Generator

Rating
1475 ekW Continuous
Rating
1475 ekW Continuous
Voltage
230 - 480 V
Constructions
Double bearing, close coupled
Insulation
Class H
Continuous (50 and 60Hz)
1475kW / 1844KVA
No. of poles
4
Excitation
Static regulated brushless PM excited
Frame Size
826
Pitch
0.6667
Alignment
Pilot shaft
Overspeed capability – % of rated
125% of rated
Frequency
50/60 Hz
Voltage 60Hz
480/240V
Frequency
50/60 Hz Switchable
Voltage regulator
3 phase sensing with Volts-per-Hertz
Voltage regulation
Less than ± 0.5% voltage gain Adjustable to compensate for engine speed droop and line loss
Wave form deviation
Less than 3% deviation
Telephone Influence Factor (TIF)
Less than 50
Harmonic Distortion (THD)
Less than 5%

Engine

Engine
Cat G3516C Low Emissions Gas Engine
Engine
Cat G3516C Low Emissions Gas Engine
Fuel
Natural Gas
Fuel
Natural Gas
Number of Cylinders
V16
Bore
6.7 in
Stroke
7.5 in
Displacement
4210 cu in
Compression ratio
11.3:1
Engine Speed (rpm)
1500/1800
Aspiration
Turbocharged Separate Circuit Aftercooled
Aftercooler Inlet (deg C)
92
Jacket Water Outlet (deg C)
98
Exhaust Manifold
Dry
Fuel system
Cat Low Pressure w/ Air Fuel Ratio Control
Governor type
ADEM™ A3 Control System
Combustion
Low Emission
Fuel Pressure Range (PSI)
3-7
Methane Number
55-100

Dimensions

Width
96 in
Width
96 in
Height
114 in
Height
114 in
Length
480 in
Length
480 in
Weight
70372 lb
Weight
70372 lb

Dimension

Weight (w/Chassis) (w/ lube, oil and coolant)
79372 lb
  • Engine
    • Cat G3516C Island Mode Gas Engine (Operates on 31.5 to 47.2 MJ/Nm3 (800 to 1200 btu/ft3) dry pipeline natural gas) .
  • Generator
    • Double bearing SR-4B brushless, form wound, permanent magnet excited, three-phase with Cat digital voltage regulator (Cat DVR), space heater, 6-lead design, Class H insulation operating at Class F temperature for extended life, winding temperature detecto
  • Containerized Module
    • 40' ISO high cube container, 9-high stack CSC certified.
  • Cooling
    • Standard cooling provides 40C (104F) ambient capability with 500mg/Nm3 NOx at 100% Continuous.
  • Generator Controls and Protection
    • Controls provide auto paralleling AGC-4 controller, CAN-bus, ethernet comm, PWM and analog outputs, legacy analog load sharing; includes PL1000E gas engine Advisor panel for operational/diagnostic information; cabinet houses shore power transformer, dis
  • Utility Multi-Functional Relay
    • Intertie protection provided via utility grade Basler BE1-11i
  • Trailer
    • 3-axle chassis
    • Ladders, handrails, internal storage provisions
Get in touch Your Nearest Location