Technical Summary

Configuration
Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications
IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure
NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature
0 degrees to 50 degrees C
Storage Temperature
-20 degrees C to +60 degrees C
Low Voltage Standards
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Choice of 19” Surface Acoustic Wave Color or 15” Resistive Color Touchscreen
  • User selected Multi-function Relay (utility grade)
  • Circuit Breaker Control Switch with indicators
  • Audible Alarm & Horn Silence Button
  • Emergency Stop Button for each generator
  • Instant Auto Switch to Return System to Ready State
  • Generator Demand Priority Control
    • Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
  • Redundant Touchscreens
  • Redundant Communication Networks
  • ATS and UPS Communication & Display
  • Data Table Interface
    • Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
  • Historical Trending (19” Touchscreen)
  • Remote Event Notification
  • Utility Interconnect Multi-function Relay (Utility Grade)
  • Supplemental Hardware Synchronization check relay (ANSI 25 Device)
    • Provides additional discrete synchronization protection
  • Remote Power Monitoring System
    • To monitor breaker status, alarms, metering and other operating parameters
  • Distribution Breaker monitoring and control NFPA Compliant JCAHO Reporting
  • Long Term Historical Trending