Technical Summary

Rating Range
100 to 1200A
Transfer Type
Bypass Isolation
Switch Type
Contactor Based

Ratings

Control Power
100-1200A 2-, 3-, 4-pole
System Voltage Application
120 - 600 Vac, 50/60 Hz
Withstand
Up to 65 kAIC withstand
Applicable Testing
CSA C22.2 No. 178 certified
IBC 2006, CBC 2007 and OSHPD
  • Controls and Wiring
    • All controls relays and industrial grade relays are totally encapsulated to minimize exposure to dust and dirt. Lugs are 90º rated and all control wire is #16 AWG, type XLPE with a 125º temperature rating.
  • Enclosure
    • Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges to ensure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal for easy wall mounting or service and are supplied with pad-lockable latches.
  • Available Options
    • Drawout capabilities on both ATS bypass portions and power switching devices completely interchangeable between ATS and bypass units
    • Open, closed or delayed transition
    • 2- or 4-position test switch
    • Multi-meter options available
    • Selectable automatic or non-automatic operation
    • Space heaters
    • Load sequencing contacts
    • Surge suppression
    • Remote communications
    • Seismic Zone 4 Qualified (BOCA, CBC, IBC, UBC and OSHPD)
    • Field selectable, multi ratio, control voltage transformer 50/60 Hz
    • Dual drawout type is field configurable for top or bottom conduit entry
  • Optional Delayed Transition includes:
    • Time delay neutral
    • Pre-transfer signal with 1 N.O. and 1 N.C. contacts